Conduit fill and space factor — how many cables actually fit.

Pick a conduit, add your cables, get the space factor against AS/NZS 3000. Space factor is total cable area ÷ conduit internal area — keep it at or below your limit (40% is the common working figure) so cables draw in and heat gets away.

Custom cable
enter overall Ø
Reference — guide values

Conduit internal area & usable space (medium-duty PVC)

ConduitInternal ØInternal areaUsable @ 40%2.5mm² singles @ 40%

Internal diameters are typical medium-duty rigid PVC; light-duty is larger inside, heavy-duty smaller. "2.5 mm² singles" assumes 3.6 mm overall diameter per conductor — always leave room for the earth and for drawing in.

Quick answers

Conduit fill, plainly.

What's the maximum conduit fill in Australia?

AS/NZS 3000 controls cables in an enclosure by space factor — total cable area ÷ conduit internal area — not by a single fixed percentage like the US NEC. A 40% space factor is the common working figure so cables draw in and heat escapes; grouped runs go lower. Follow the conduit maker's fill data and derate for grouping.

How do I calculate conduit fill?

Add the overall area of every cable (area = π ÷ 4 × overall ز, using the insulated outer diameter, not the copper size), divide by the conduit's internal area, ×100 for the percentage. Keep it at or below your limit.

How many 2.5 mm² cables fit in 20 mm conduit?

A 20 mm MD conduit is ~16.5 mm inside (~214 mm²). At 40% that's ~86 mm² usable, and a 2.5 mm² single is ~10.2 mm² — so about 8, fewer once you count the earth and easy drawing.

Planning a bigger job?

Sizing the cables themselves? Use the cable size & voltage drop calculator. Need it installed? We match Adelaide electricians who quote before they start.

Disclaimer. This calculator provides general estimates for guidance only and is not professional, engineering or electrical design advice. Conduit and cable dimensions are typical guide values that vary by duty and brand. All results must be independently verified by a licensed electrical worker against the current editions of AS/NZS 3000, AS/NZS 3008, the conduit manufacturer's fill data and every other applicable standard for the specific installation. Electrical work must be carried out by a suitably licensed person. Find My Sparky gives no warranty as to accuracy and accepts no liability for any loss, damage, injury or non-compliance arising from use of this tool.