Find My Sparky

Cable & demand calculators In Beta

Cable size · voltage drop · max demand. Built for the ute, not the office.
Launching soonGet matched ↗
Free sparky tools

Cable size, voltage drop, max demand and kW ↔ amps — sorted in seconds.

Four calculators based on AS/NZS 3000 and AS/NZS 3008 methodology. Voltage drop limit is 5% of nominal supply voltage (11.5 V on 230 V single-phase). Copper conductors at 75°C operating temperature.

Single domestic installation — AS/NZS 3000 Appendix C, Table C1 methodology. Enter what's connected; factors apply automatically.

Lighting points
3 A first 20 pts + 2 A per extra 20
Socket outlets (10 A points)
10 A first 20 pts + 5 A per extra 20
Cooking appliances — total connected (kW)
50% of connected load
Aircon / fixed space heating — total (A)
75% of connected load
Storage hot water (A)
100% of connected load
EV charger (A)
100% — continuous load
Pool / spa equipment (A)
100% of connected load
Other fixed loads (A)
100% of connected load

Enter any one of kW, kVA or amps — the other two update live. Real power (kW) uses power factor; apparent power (kVA) does not.

Enter any value

Power factor guide: resistive loads (heaters, ovens) ≈ 1.0; motors, aircon and mixed loads ≈ 0.8. DC has no power factor and no kVA.

Reference — guide values

Current-carrying capacity, copper V-90 (A)

Size mm²Clipped directIn conduitPartial thermal insulationmV/A·m (1φ)mV/A·m (3φ)

Single circuit, 40°C ambient, guide values only. mV/A·m derived from conductor resistance at 75°C, unity power factor — matches AS/NZS 3008 tabulated values within ~2% up to 35 mm²; above 50 mm² cable reactance adds to the tabulated figure, so check the standard.

Quick answers

Voltage drop and cable sizing, plainly.

What's the maximum voltage drop allowed?

AS/NZS 3000 requires no more than 5% below nominal supply voltage at any point of the installation — 11.5 V on 230 V single-phase, 20 V on 400 V three-phase. A common design split is 2% for mains and submains, 3% for final subcircuits.

How is voltage drop calculated?

Vd = current × route length × the cable's mV/A·m value ÷ 1000. A 32 A load over 25 m of 6 mm² copper (~7.5 mV/A·m single-phase) drops about 6 V — 2.6% of 230 V, so it passes a 3% subcircuit limit with little margin.

What cable size for a 7 kW EV charger?

About 32 A continuous. 6 mm² copper suits short dedicated runs; voltage drop typically pushes 30–40 m runs to 10 mm². Planning one? We match EV charger installers in Adelaide.

Why does max demand matter?

Calculated maximum demand sizes your consumer mains, main switch and switchboard. Adding an EV charger or big aircon can tip an older 63 A supply over its limit — that's when a switchboard upgrade conversation starts.

How do I convert kW to amps?

Single-phase: amps = 1000 × kW ÷ (V × PF). Three-phase: amps = 1000 × kW ÷ (√3 × V × PF). DC: amps = 1000 × kW ÷ V. So 10 kW single-phase at 230 V, PF 0.8, draws about 54 A. The converter tab does it both ways.

What's the difference between kW and kVA?

kVA is apparent power (volts × amps); kW is real power (kVA × power factor). They're equal only when power factor is 1. Switchboards and supply are sized on kVA/amps, so amps ↔ kVA is the conversion that sizes the main switch.

Disclaimer. This calculator provides general estimates for guidance only and is not professional, engineering or electrical design advice. All results must be independently verified by a licensed electrical worker against the current editions of AS/NZS 3000, AS/NZS 3008 and every other applicable standard and regulation for the specific installation. Electrical work must be carried out by a suitably licensed person. Find My Sparky gives no warranty as to accuracy and accepts no liability for any loss, damage, injury or non-compliance arising from use of this tool.