Solar voltage rise · AS/NZS 3008

Follow the inverter path. Segment by segment.

Model the point of supply to inverter path, see every cable contribution and apply export limiting only where it belongs.

Generation and cable path

Use the combined inverter rating if multiple inverters share this path.

01 · Inverter current

Single-phase uses I = P / V. Three-phase uses I = P / (√3 × V). Power factor is 1 for kW ratings.

02 · Each cable segment

Rise is I × L × 2Z / 1000 for single-phase or I × L × √3Z / 1000 for three-phase, divided by parallel cables.

03 · Export limiting

Only the point-of-supply to main-switchboard segment is reduced. Downstream cables may carry full inverter output consumed on site.

Design limitation. Current-carrying capacity is not checked on this page. Confirm cable ratings, inverter manufacturer limits, service and network requirements, phase balance, power quality and the complete current AS/NZS 3008 and AS/NZS 4777.1 requirements.